ODRA – Medium voltage switchgears

Medium voltage air insulated metal-clad switchgear ODRA are designed for primary distribution of AC three-phase electric energy with a rated frequency of 50/60 Hz and rated voltage up to 36 (40,5 kV) in power plants, distribution networks of public utilities and industrial power engineering sectors. Switchgear may be executed either in free standing or against wall setup. The ODRA switchgear may be applied for operation in both standards and special conditions.

The construction is made from steel plates covered by aluminum-zinc coating. Side covers of the external panels and doors are covered with polyester powder paint, which ensures excellent protection from corrosion.
The color is adapted to the Customer needs. Switchgears are designed for installation in electrical rooms.

Switchgear ODRA were type tested and come with the certificates verifying their rated parameters and admitting them for use at power distribution plants, power stations, industrial plants and other facilities generating, transmitting or using electric energy.

ODRA construction with withdrawal element.

A – Bus-bar compartment;

B – withdrawal element compartment;

C – cable connection compartment;

D – secondary wiring compartment;

On the trolley can be installed circuit breaker, disconnector, contactor, instrument voltage transformers.

 

TECHNINIAI DATA

ODRA 12
ODRA 17
ODRA 24
ODRA 36(40,5)

Add Yor Heading Text Here 
Rated insulation voltagekVup to 12up to 17,5up to 24up to 36/40,5*
Rated lightning impulse withstand voltage (1,2/50μs)kV75/8595/110125/145170/190*
Rated power frequency withstand voltagekV28/32

42/48*

38/4550/6070/95*
Rated frequencyHz50
Rated continuous currentAup to 3150up to 2500up to 2000up to 1250
Rated short time withstand currentup to 31,5/3s

up to 40/1s

up to 31,5/3sup to 25/3s
Rated peak withstand currentup to 100up to 80up to 63
Withstand for internal arcing faultup to 40/1sup to 31,5/1sup to 25/1s
Degree of protectionIP 41/IP4X
IAC classification (class of resistance to internal arc)AFLR
PM/PI classification (class of partitions)PM
LSC classification (class of compartment accessibility)LSC2B
Weightkg550-1200900-1600
Bus-bar systemsingle
Overall dimensions**)Widthmm600-1000750-10001200,1600
Depthmm1250,145014301950
Heightmm2150,225023002500
StandardsPN-EN 62271-200:2007PN-EN 62271-1:2009

ГОСТ 14693:1990

ГОСТ 1516.3:1996

*) required according to GOST
**) without external guards, covers, doors

 

 

Environmental operating conditions
Switchgear ODRA with installed equipment are adapted for indoor operation under normal conditions, with the following environmental conditions:

Installation altitude above sea level
to 1000 m
Ambient temperature:
peak short-time
+40°C
maximum average during the day
+35°C
maximum average yearly
+20°C
minimum sustained
-5°C
Air relative humidity at +40°C:
during the start up
max. 80%
during standstill or operation
max. 95%